Vulnerabilities
CVE-2022-3192
MEDIUMImproper Input Validation vulnerability in ABB AC500 V2 PM5xx allows Client-Server Protocol Manipulation.This issue affects AC500 V2: from 2.0.0 before 2.8.6.
CVE-2023-1258
MEDIUMExposure of Sensitive Information to an Unauthorized Actor vulnerability in ABB Flow-X firmware on Flow-X embedded hardware (web service modules) allows Footprinting.This issue affects Flow-X: before 4.0.
CVE-2022-4126
CRITICALUse of Default Password vulnerability in ABB RCCMD on Windows, Linux, MacOS allows Try Common or Default Usernames and Passwords.This issue affects RCCMD: before 4.40 230207.
CVE-2022-26080
MEDIUMUse of Insufficiently Random Values vulnerability in ABB Pulsar Plus System Controller NE843_S, ABB Infinity DC Power Plant.This issue affects Pulsar Plus System Controller NE843_S : comcode 150042936; Infinity DC Power Plant: H5692448 G104 G842 G224L G630-4 G451C(2) G461(2) – comcode 150047415.
CVE-2023-0228
HIGHImproper Authentication vulnerability in ABB Symphony Plus S+ Operations.This issue affects Symphony Plus S+ Operations: from 2.X through 2.1 SP2, 2.2, from 3.X through 3.3 SP1, 3.3 SP2.
CVE-2021-22283
MEDIUMImproper Initialization vulnerability in ABB Relion protection relays - 611 series, ABB Relion protection relays - 615 series IEC 4.0 FP1, ABB Relion protection relays - 615 series CN 4.0 FP1, ABB Relion protection relays - 615 series IEC 5.0, ABB Relion protection relays - 615 series IEC 5.0 FP1, ABB Relion protection relays - 620 series IEC/CN 2.0, ABB Relion protection relays - 620 series IEC/CN 2.0 FP1, ABB Relion protection relays - REX640 PCL1, ABB Relion protection relays - REX640 PCL2, ABB Relion protection relays - REX640 PCL3, ABB Relion protection relays - RER615, ABB Remote Monitoring and Control - REC615, ABB Merging Unit- SMU615 allows Communication Channel Manipulation.This issue affects Relion protection relays - 611 series: from 1.0.0 before 2.0.3; Relion protection relays - 615 series IEC 4.0 FP1: from 4.1.0 before 4.1.9; Relion protection relays - 615 series CN 4.0 FP1: from 4.1.0 before 4.1.8; Relion protection relays - 615 series IEC 5.0: from 5.0.0 before 5.0.12; Relion protection relays - 615 series IEC 5.0 FP1: from 5.1.0 before 5.1.20; Relion protection relays - 620 series IEC/CN 2.0: from 2.0.0 before 2.0.11; Relion protection relays - 620 series IEC/CN 2.0 FP1: from 2.1.0 before 2.1.15; Relion protection relays - REX640 PCL1: from 1.0.0 before 1.0.8; Relion protection relays - REX640 PCL2: from 1.1.0 before 1.1.4; Relion protection relays - REX640 PCL3: from 1.2.0 before 1.2.1; Relion protection relays - RER615: from 2.0.0 before 2.0.3; Remote Monitoring and Control - REC615: from 1.0.0 before 2.0.3; Merging Unit- SMU615: from 1.0.0 before 1.0.2.
CVE-2022-1607
MEDIUMCross-Site Request Forgery (CSRF) vulnerability in ABB Pulsar Plus System Controller NE843_S, ABB Infinity DC Power Plant allows Cross Site Request Forgery.This issue affects Pulsar Plus System Controller NE843_S : comcode 150042936; Infinity DC Power Plant: H5692448 G104 G842 G224L G630-4 G451C(2) G461(2) – comcode 150047415.
CVE-2022-34838
HIGHStoring Passwords in a Recoverable Format vulnerability in ABB Zenon 8.20 allows an attacker who successfully exploit the vulnerability may add or alter data points and corresponding attributes. Once such engineering data is used the data visualization will be altered for the end user.
CVE-2022-34836
MEDIUMRelative Path Traversal vulnerability in ABB Zenon 8.20 allows the user to access files on the Zenon system and user also can add own log messages and e.g., flood the log entries. An attacker who successfully exploit the vulnerability could access the Zenon runtime activities such as the start and stop of various activity and the last error code etc.
CVE-2022-34837
MEDIUMStoring Passwords in a Recoverable Format vulnerability in ABB Zenon 8.20 allows an attacker who successfully exploit the vulnerability may add more network clients that may monitor various activities of the Zenon.
CVE-2022-0902
HIGHImproper Limitation of a Pathname to a Restricted Directory ('Path Traversal'), Improper Neutralization of Special Elements used in a Command ('Command Injection') vulnerability in flow computer and remote controller products of ABB ( RMC-100 (Standard), RMC-100-LITE, XIO, XFCG5 , XRCG5 , uFLOG5 , UDC) allows an attacker who successfully exploited this vulnerability could insert and run arbitrary code in an affected system node.
CVE-2022-1596
MEDIUMIncorrect Permission Assignment for Critical Resource vulnerability in ABB REX640 PCL1, REX640 PCL2, REX640 PCL3 allows an authenticated attacker to launch an attack against the user database file and try to take control of an affected system node.
CVE-2022-31219
HIGHVulnerabilities in the Drive Composer allow a low privileged attacker to create and write to a file anywhere on the file system as SYSTEM with arbitrary content as long as the file does not already exist. The Drive Composer installer file allows a low-privileged user to run a "repair" operation on the product.
CVE-2022-31218
HIGHVulnerabilities in the Drive Composer allow a low privileged attacker to create and write to a file anywhere on the file system as SYSTEM with arbitrary content as long as the file does not already exist. The Drive Composer installer file allows a low-privileged user to run a "repair" operation on the product.
CVE-2022-31217
HIGHVulnerabilities in the Drive Composer allow a low privileged attacker to create and write to a file anywhere on the file system as SYSTEM with arbitrary content as long as the file does not already exist. The Drive Composer installer file allows a low-privileged user to run a "repair" operation on the product.
CVE-2022-31216
HIGHVulnerabilities in the Drive Composer allow a low privileged attacker to create and write to a file anywhere on the file system as SYSTEM with arbitrary content as long as the file does not already exist. The Drive Composer installer file allows a low-privileged user to run a "repair" operation on the product.
CVE-2022-26057
MEDIUMVulnerabilities in the Mint WorkBench allow a low privileged attacker to create and write to a file anywhere on the file system as SYSTEM with arbitrary content as long as the file does not already exist. The Mint WorkBench installer file allows a low-privileged user to run a "repair" operation on the product
CVE-2022-29483
HIGHIncorrect Default Permissions vulnerability in ABB e-Design allows attacker to install malicious software executing with SYSTEM permissions violating confidentiality, integrity, and availability of the target machine.
CVE-2022-28702
MEDIUMIncorrect Default Permissions vulnerability in ABB e-Design allows attacker to install malicious software executing with SYSTEM permissions violating confidentiality, integrity, and availability of the target machine.
CVE-2022-0947
CRITICALA vulnerability in ABB ARG600 Wireless Gateway series that could allow an attacker to exploit the vulnerability by remotely connecting to the serial port gateway, and/or protocol converter, depending on the configuration.
CVE-2021-22277
HIGHImproper Input Validation vulnerability in ABB 800xA, Control Software for AC 800M, Control Builder Safe, Compact Product Suite - Control and I/O, ABB Base Software for SoftControl allows an attacker to cause the denial of service.
CVE-2021-22284
HIGHIncorrect Permission Assignment for Critical Resource vulnerability in OPC Server for AC 800M allows an attacker to execute arbitrary code in the node running the AC800M OPC Server.
CVE-2021-22285
HIGHImproper Handling of Exceptional Conditions, Improper Check for Unusual or Exceptional Conditions vulnerability in the ABB SPIET800 and PNI800 module that allows an attacker to cause the denial of service or make the module unresponsive.
CVE-2021-22288
HIGHImproper Input Validation vulnerability in the ABB SPIET800 and PNI800 module allows an attacker to cause the denial of service or make the module unresponsive.
CVE-2021-22286
HIGHImproper Input Validation vulnerability in the ABB SPIET800 and PNI800 module allows an attacker to cause the denial of service or make the module unresponsive.
CVE-2021-22279
CRITICALA Missing Authentication vulnerability in RobotWare for the OmniCore robot controller allows an attacker to read and modify files on the robot controller if the attacker has access to the Connected Services Gateway Ethernet port.
CVE-2021-22278
MEDIUMA certificate validation vulnerability in PCM600 Update Manager allows attacker to get unwanted software packages to be installed on computer which has PCM600 installed.
CVE-2021-22272
MEDIUMThe vulnerability origins in the commissioning process where an attacker of the ControlTouch can enter a serial number in a specific way to transfer the device virtually into her/his my.busch-jaeger.de or mybuildings.abb.com profile. A successful attacker can observe and control a ControlTouch remotely under very specific circumstances. The issue is fixed in the cloud side of the system. No firmware update is needed for customer products. If a user wants to understand if (s)he is affected, please read the advisory. This issue affects: ABB and Busch-Jaeger, ControlTouch
CVE-2021-22276
MEDIUMThe vulnerability allows a successful attacker to bypass the integrity check of FW uploaded to the free@home System Access Point.
CVE-2020-24672
CRITICALA vulnerability in Base Software for SoftControl allows an attacker to insert and run arbitrary code in a computer running the affected product. This issue affects: .
CVE-2020-24686
HIGHThe vulnerabilities can be exploited to cause the web visualization component of the PLC to stop and not respond, leading to genuine users losing remote visibility of the PLC state. If a user attempts to login to the PLC while this vulnerability is exploited, the PLC will show an error state and refuse connections to Automation Builder. The execution of the PLC application is not affected by this vulnerability. This issue affects ABB AC500 V2 products with onboard Ethernet.
CVE-2020-24685
HIGHAn unauthenticated specially crafted packet sent by an attacker over the network will cause a denial-of-service (DoS) vulnerability. Vulnerability allows attacker to stop the PLC. After stopping (ERR LED flashing red), physical access to the PLC is required in order to restart the application. This issue affects: ABB AC500 V2 products with onboard Ethernet version 2.8.4 and prior versions.
CVE-2020-24675
CRITICALIn S+ Operations and S+ History, it is possible that an unauthenticated user could inject values to the Operations History server (or standalone S+ History server) and ultimately write values to the controlled process.
CVE-2020-24673
CRITICALIn S+ Operations and S+ Historian, a successful SQL injection exploit can read sensitive data from the database, modify database data (Insert/Update/Delete), execute administration operations on the database (such as shutdown the DBMS), recover the content of a given file present on the DBMS file system and in some cases issue commands to the operating system. This can lead to a loss of confidentiality and data integrity or even affect the product behavior and its availability.
CVE-2020-24674
HIGHIn S+ Operations and S+ Historian, not all client commands correctly check user permission as expected. Authenticated but Unauthorized remote users could execute a Denial-of-Service (DoS) attack, execute arbitrary code, or obtain more privilege than intended on the machines.
CVE-2020-24683
CRITICALThe affected versions of S+ Operations (version 2.1 SP1 and earlier) used an approach for user authentication which relies on validation at the client node (client-side authentication). This is not as secure as having the server validate a client application before allowing a connection. Therefore, if the network communication or endpoints for these applications are not protected, unauthorized actors can bypass authentication and make unauthorized connections to the server application.
CVE-2020-24680
HIGHIn S+ Operations and S+ Historian, the passwords of internal users (not Windows Users) are encrypted but improperly stored in a database.
CVE-2020-24679
HIGHA S+ Operations and S+ Historian service is subject to a DoS by special crafted messages. An attacker might use this flaw to make it crash or even execute arbitrary code on the machine where the service is hosted.
CVE-2020-24677
HIGHVulnerabilities in the S+ Operations and S+ Historian web applications can lead to a possible code execution and privilege escalation, redirect the user somewhere else or download unwanted data.
CVE-2020-24676
HIGHIn Symphony Plus Operations and Symphony Plus Historian, some services can be vulnerable to privilege escalation attacks. An unprivileged (but authenticated) user could execute arbitrary code and result in privilege escalation, depending on the user that the service runs as.
CVE-2020-24678
HIGHAn authenticated user might execute malicious code under the user context and take control of the system. S+ Operations or S+ Historian database is affected by multiple vulnerabilities such as the possibility to allow remote authenticated users to gain high privileges.
CVE-2020-10287
CRITICALThe IRC5 family with UAS service enabled comes by default with credentials that can be found on publicly available manuals. ABB considers this a well documented functionality that helps customer set up however, out of our research, we found multiple production systems running these exact default credentials and consider thereby this an exposure that should be mitigated. Moreover, future deployments should consider that these defaults should be forbidden (user should be forced to change them).
CVE-2020-10288
CRITICALIRC5 exposes an ftp server (port 21). Upon attempting to gain access you are challenged with a request of username and password, however you can input whatever you like. As long as the field isn't empty it will be accepted.
CVE-2020-8482
HIGHInsecure storage of sensitive information in ABB Device Library Wizard versions 6.0.X, 6.0.3.1 and 6.0.3.2 allows unauthenticated low privilege user to read file that contains confidential data
CVE-2019-5620
UNKNOWNABB MicroSCADA Pro SYS600 version 9.3 suffers from an instance of CWE-306: Missing Authentication for Critical Function.
CVE-2020-8489
HIGHInsufficient protection of the inter-process communication functions in ABB System 800xA Information Management (all published versions) enables an attacker authenticated on the local system to inject data, affecting the runtime values to be stored in the archive, or making Information Management history services unavailable.
CVE-2020-8488
HIGHInsufficient protection of the inter-process communication functions in ABB System 800xA Batch Management (all published versions) enables an attacker authenticated on the local system to inject data, affecting User Interface update during batch execution and/or compare/printing functionalities.
CVE-2020-8487
MEDIUMInsufficient protection of the inter-process communication functions in ABB System 800xA Base (all published versions) enables an attacker authenticated on the local system to inject data, affect node redundancy handling.
CVE-2020-8486
MEDIUMInsufficient protection of the inter-process communication functions in ABB System 800xA RNRP (all published versions) enables an attacker authenticated on the local system to inject data, affect node redundancy handling.
CVE-2020-8485
HIGHInsufficient protection of the inter-process communication functions in ABB System 800xA for MOD 300 (all published versions) enables an attacker authenticated on the local system to inject data, allowing reads and writes to the controllers or cause windows processes to crash.