Vulnerabilities
CVE-2024-5988
UNKNOWNDue to an improper input validation, an unauthenticated threat actor can send a malicious message to invoke a local or remote executable and cause a remote code execution condition on the Rockwell Automation ThinManager® ThinServer™.
CVE-2024-37369
UNKNOWNA privilege escalation vulnerability exists in the affected product. The vulnerability allows low-privilege users to edit scripts, bypassing Access Control Lists, and potentially gaining further access within the system.
CVE-2024-5659
UNKNOWNRockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised.
CVE-2024-37368
UNKNOWNA user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.
CVE-2024-37367
UNKNOWNA user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE v12. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. This action is allowed without proper authentication verification.
CVE-2024-3640
UNKNOWNAn unquoted executable path exists in the Rockwell Automation FactoryTalk® Remote Access™ possibly resulting in remote code execution if exploited. While running the FTRA installer package, the executable path is not properly quoted, which could allow a threat actor to enter a malicious executable and run it as a System user. A threat actor needs admin privileges to exploit this vulnerability.
CVE-2024-4609
UNKNOWNA vulnerability exists in the Rockwell Automation FactoryTalk® View SE Datalog function that could allow a threat actor to inject a malicious SQL statement if the SQL database has no authentication in place or if legitimate credentials were stolen. If exploited, the attack could result in information exposure, revealing sensitive information. Additionally, a threat actor could potentially modify and delete the data in a remote database. An attack would only affect the HMI design time, not runtime.
CVE-2024-2424
HIGHAn input validation vulnerability exists in the Rockwell Automation 5015-AENFTXT that causes the secondary adapter to result in a major nonrecoverable fault (MNRF) when malicious input is entered. If exploited, the availability of the device will be impacted, and a manual restart is required. Additionally, a malformed PTP packet is needed to exploit this vulnerability.
CVE-2024-3493
HIGHA specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation's ControlLogix 5580, Guard Logix 5580, CompactLogix 5380, and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices.
CVE-2024-2929
HIGHA memory corruption vulnerability in Rockwell Automation Arena Simulation software could potentially allow a malicious user to insert unauthorized code to the software by corrupting the memory triggering an access violation. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2024-21920
MEDIUMA memory buffer vulnerability in Rockwell Automation Arena Simulation could potentially let a threat actor read beyond the intended memory boundaries. This could reveal sensitive information and even cause the application to crash, resulting in a denial-of-service condition. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2024-21919
HIGHAn uninitialized pointer in Rockwell Automation Arena Simulation software could potentially allow a malicious user to insert unauthorized code to the software by leveraging the pointer after it is properly. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2024-21918
HIGHA memory buffer vulnerability in Rockwell Automation Arena Simulation software could potentially allow a malicious user to insert unauthorized code to the software by corrupting the memory and triggering an access violation. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2024-21913
HIGHA heap-based memory buffer overflow vulnerability in Rockwell Automation Arena Simulation software could potentially allow a malicious user to insert unauthorized code into the software by overstepping the memory boundaries, which triggers an access violation. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2024-21912
HIGHAn arbitrary code execution vulnerability in Rockwell Automation Arena Simulation could let a malicious user insert unauthorized code into the software. This is done by writing beyond the designated memory area, which causes an access violation. Once inside, the threat actor can run harmful code on the system. This affects the confidentiality, integrity, and availability of the product. To trigger this, the user would unwittingly need to open a malicious file shared by the threat actor.
CVE-2024-21914
MEDIUMA vulnerability exists in the affected product that allows a malicious user to restart the Rockwell Automation PanelView™ Plus 7 terminal remotely without security protections. If the vulnerability is exploited, it could lead to the loss of view or control of the PanelView™ product.
CVE-2024-2427
HIGHA denial-of-service vulnerability exists in the Rockwell Automation PowerFlex® 527 due to improper traffic throttling in the device. If multiple data packets are sent to the device repeatedly the device will crash and require a manual restart to recover.
CVE-2024-2426
HIGHA denial-of-service vulnerability exists in the Rockwell Automation PowerFlex® 527 due to improper input validation in the device. If exploited, a disruption in the CIP communication will occur and a manual restart will be required by the user to recover it.
CVE-2024-2425
HIGHA denial-of-service vulnerability exists in the Rockwell Automation PowerFlex® 527 due to improper input validation in the device. If exploited, the web server will crash and need a manual restart to recover it.
CVE-2024-21915
CRITICALA privilege escalation vulnerability exists in Rockwell Automation FactoryTalk® Service Platform (FTSP). If exploited, a malicious user with basic user group privileges could potentially sign into the software and receive FTSP Administrator Group privileges. A threat actor could potentially read and modify sensitive data, delete data and render the FTSP system unavailable.
CVE-2024-21916
HIGHA denial-of-service vulnerability exists in specific Rockwell Automation ControlLogix ang GuardLogix controllers. If exploited, the product could potentially experience a major nonrecoverable fault (MNRF). The device will restart itself to recover from the MNRF.
CVE-2024-21917
CRITICALA vulnerability exists in Rockwell Automation FactoryTalk® Service Platform that allows a malicious user to obtain the service token and use it for authentication on another FTSP directory. This is due to the lack of digital signing between the FTSP service token and directory. If exploited, a malicious user could potentially retrieve user information and modify settings without any authentication.
CVE-2023-5909
HIGHKEPServerEX does not properly validate certificates from clients which may allow unauthenticated users to connect.
CVE-2023-5908
CRITICALKEPServerEX is vulnerable to a buffer overflow which may allow an attacker to crash the product being accessed or leak information.
CVE-2023-27858
HIGHRockwell Automation Arena Simulation contains an arbitrary code execution vulnerability that could potentially allow a malicious user to commit unauthorized code to the software by using an uninitialized pointer in the application. The threat-actor could then execute malicious code on the system affecting the confidentiality, integrity, and availability of the product. The user would need to open a malicious file provided to them by the attacker for the code to execute.
CVE-2023-27854
HIGHAn arbitrary code execution vulnerability was reported to Rockwell Automation in Arena Simulation that could potentially allow a malicious user to commit unauthorized arbitrary code to the software by using a memory buffer overflow. The threat-actor could then execute malicious code on the system affecting the confidentiality, integrity, and availability of the product. The user would need to open a malicious file provided to them by the attacker for the code to execute.
CVE-2023-46289
HIGHRockwell Automation FactoryTalk View Site Edition insufficiently validates user input, which could potentially allow threat actors to send malicious data bringing the product offline. If exploited, the product would become unavailable and require a restart to recover resulting in a denial-of-service condition.
CVE-2023-46290
HIGHDue to inadequate code logic, a previously unauthenticated threat actor could potentially obtain a local Windows OS user token through the FactoryTalk® Services Platform web service and then use the token to log in into FactoryTalk® Services Platform . This vulnerability can only be exploited if the authorized user did not previously log in into the FactoryTalk® Services Platform web service.
CVE-2023-29464
HIGHFactoryTalk Linx, in the Rockwell Automation PanelView Plus, allows an unauthenticated threat actor to read data from memory via crafted malicious packets. Sending a size larger than the buffer size results in leakage of data from memory resulting in an information disclosure. If the size is large enough, it causes communications over the common industrial protocol to become unresponsive to any type of packet, resulting in a denial-of-service to FactoryTalk Linx over the common industrial protocol.
CVE-2023-2262
CRITICALA buffer overflow vulnerability exists in the Rockwell Automation select 1756-EN* communication devices. If exploited, a threat actor could potentially leverage this vulnerability to perform a remote code execution. To exploit this vulnerability, a threat actor would have to send a maliciously crafted CIP request to device.
CVE-2023-29463
HIGHThe JMX Console within the Rockwell Automation Pavilion8 is exposed to application users and does not require authentication. If exploited, a malicious user could potentially retrieve other application users’ session data and or log users out of their session.
CVE-2023-2071
CRITICALRockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
CVE-2023-2917
CRITICALThe Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability. Due to an improper input validation, a path traversal vulnerability exists, via the filename field, when the ThinManager processes a certain function. If exploited, an unauthenticated remote attacker can upload arbitrary files to any directory on the disk drive where ThinServer.exe is installed. A malicious user could exploit this vulnerability by sending a crafted synchronization protocol message and potentially gain remote code execution abilities.
CVE-2023-2915
HIGHThe Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability, Due to improper input validation, a path traversal vulnerability exists when the ThinManager software processes a certain function. If exploited, an unauthenticated remote threat actor can delete arbitrary files with system privileges. A malicious user could exploit this vulnerability by sending a specifically crafted synchronization protocol message resulting in a denial-of-service condition.
CVE-2023-2914
HIGHThe Rockwell Automation Thinmanager Thinserver is impacted by an improper input validation vulnerability, an integer overflow condition exists in the affected products. When the ThinManager processes incoming messages, a read access violation occurs and terminates the process. A malicious user could exploit this vulnerability by sending a crafted synchronization protocol message and causing a denial of service condition in the software.
CVE-2023-2423
HIGHA vulnerability was discovered in the Rockwell Automation Armor PowerFlex device when the product sends communications to the local event log. Threat actors could exploit this vulnerability by sending an influx of network commands, causing the product to generate an influx of event log traffic at a high rate. If exploited, the product would stop normal operations and self-reset creating a denial-of-service condition. The error code would need to be cleared prior to resuming normal operations.
CVE-2023-2913
HIGHAn executable used in Rockwell Automation ThinManager ThinServer can be configured to enable an API feature in the HTTPS Server Settings. This feature is disabled by default. When the API is enabled and handling requests, a path traversal vulnerability exists that allows a remote actor to leverage the privileges of the server’s file system and read arbitrary files stored in it. A malicious user could exploit this vulnerability by executing a path that contains manipulating variables.
CVE-2023-2263
HIGHThe Rockwell Automation Kinetix 5700 DC Bus Power Supply Series A is vulnerable to CIP fuzzing. The new ENIP connections cannot be established if impacted by this vulnerability, which prohibits operational capabilities of the device resulting in a denial-of-service attack.
CVE-2023-3596
HIGHWhere this vulnerability exists in the Rockwell Automation 1756-EN4* Ethernet/IP communication products, it could allow a malicious user to cause a denial of service by asserting the target system through maliciously crafted CIP messages.
CVE-2023-3595
CRITICALWhere this vulnerability exists in the Rockwell Automation 1756 EN2* and 1756 EN3* ControlLogix communication products, it could allow a malicious user to perform remote code execution with persistence on the target system through maliciously crafted CIP messages. This includes the ability to modify, deny, and exfiltrate data passing through the device.
CVE-2023-2746
CRITICALThe Rockwell Automation Enhanced HIM software contains an API that the application uses that is not protected sufficiently and uses incorrect Cross-Origin Resource Sharing (CORS) settings and, as a result, is vulnerable to a Cross Site Request Forgery (CSRF) attack. To exploit this vulnerability, a malicious user would have to convince a user to click on an untrusted link through a social engineering attack or successfully perform a Cross Site Scripting Attack (XSS). Exploitation of a CSRF could potentially lead to sensitive information disclosure and full remote access to the affected products.
CVE-2023-2072
HIGHThe Rockwell Automation PowerMonitor 1000 contains stored cross-site scripting vulnerabilities within the web page of the product. The vulnerable pages do not require privileges to access and can be injected with code by an attacker which could be used to leverage an attack on an authenticated user resulting in remote code execution and potentially the complete loss of confidentiality, integrity, and availability of the product.
CVE-2023-2778
HIGHA denial-of-service vulnerability exists in Rockwell Automation FactoryTalk Transaction Manager. This vulnerability can be exploited by sending a modified packet to port 400. If exploited, the application could potentially crash or experience a high CPU or memory usage condition, causing intermittent application functionality issues. The application would need to be restarted to recover from the DoS.
CVE-2023-2639
MEDIUMThe underlying feedback mechanism of Rockwell Automation's FactoryTalk System Services that transfers the FactoryTalk Policy Manager rules to relevant devices on the network does not verify that the origin of the communication is from a legitimate local client device. This may allow a threat actor to craft a malicious website that, when visited, will send a malicious script that can connect to the local WebSocket endpoint and wait for events as if it was a valid client device. If successfully exploited, this would allow a threat actor to receive information including whether FactoryTalk Policy Manager is installed and potentially the entire security policy.
CVE-2023-2638
MEDIUMRockwell Automation's FactoryTalk System Services does not verify that a backup configuration archive is password protected. Improper authorization in FTSSBackupRestore.exe may lead to the loading of malicious configuration archives. This vulnerability may allow a local, authenticated non-admin user to craft a malicious backup archive, without password protection, that will be loaded by FactoryTalk System Services as a valid backup when a restore procedure takes places. User interaction is required for this vulnerability to be successfully exploited.
CVE-2023-2637
HIGHRockwell Automation's FactoryTalk System Services uses a hard-coded cryptographic key to generate administrator cookies. Hard-coded cryptographic key may lead to privilege escalation. This vulnerability may allow a local, authenticated non-admin user to generate an invalid administrator cookie giving them administrative privileges to the FactoryTalk Policy Manger database. This may allow the threat actor to make malicious changes to the database that will be deployed when a legitimate FactoryTalk Policy Manager user deploys a security policy model. User interaction is required for this vulnerability to be successfully exploited.
CVE-2023-2444
HIGHA cross site request forgery vulnerability exists in Rockwell Automation's FactoryTalk Vantagepoint. This vulnerability can be exploited in two ways. If an attacker sends a malicious link to a computer that is on the same domain as the FactoryTalk Vantagepoint server and a user clicks the link, the attacker could impersonate the legitimate user and send requests to the affected product. Additionally, if an attacker sends an untrusted link to a computer that is not on the same domain as the server and a user opens the FactoryTalk Vantagepoint website, enters credentials for the FactoryTalk Vantagepoint server, and clicks on the malicious link a cross site request forgery attack would be successful as well.
CVE-2023-2443
HIGHRockwell Automation ThinManager product allows the use of medium strength ciphers. If the client requests an insecure cipher, a malicious actor could potentially decrypt traffic sent between the client and server API.
CVE-2023-1834
CRITICALRockwell Automation was made aware that Kinetix 5500 drives, manufactured between May 2022 and January 2023, and are running v7.13 may have the telnet and FTP ports open by default. This could potentially allow attackers unauthorized access to the device through the open ports.
CVE-2023-29022
MEDIUMA cross site scripting vulnerability was discovered in Rockwell Automation's ArmorStart ST product that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.